Siemens Solar Panels direct from
Bullnet

|
 |
 |
 |
|
Fact Sheet: Sacramento Hedge Substation |
 |
|
|
Customer: |
Sacramento Municipal Utility District |
General Contractor: |
UPG |
System Type: |
1-Axis Tracking Array, Grid Tied |
Site Area: |
120,000 ft.2 (11,148 m2) |
System Size: |
254 kWpeak DC |
Total PV Array Area: |
23,400 Foot2 (2,170 meters2) |
Number of Trackers: |
20 (20 panels per tracker) |
Number of Panels: |
400 (twelve 53 watt modules per panel) |
Panel Size: |
13 ft. x 4.5 ft (3.96 m. x 1.37m.) |
Panel Power: |
636 Watts |
Number of Modules: |
4,800 |
Inverter: |
200 kW Omnion |
Utility Intertie: |
12.47 kV, 3 Phase, 60 Hz |
Structure: |
UPG Tracker, Galvanized Steel, Pressure Treated Douglas Fir |
Array Circuit Configuration: |
24 Modules in Series by 400 in Parallel |
Design AC Energy Output: |
440,000 kWh/year |
|
| |
|